Professor Emeritus:Osama El-Sayed Gouda
Electrical Power and Machines
Email :osama11***eng.cu.edu.eg
 
Qualifications
imgB.Sc. (1975) "Electrical Engineering " Cairo University (Egypt)
imgM.Sc. (1979) "Electrical Engineering " Cairo University (Egypt)
imgPh.D. (1982) "Electrical Engineering " Cairo University (Egypt)
 
Fields of Interest :
imgUnderground Power Cables
imgHigh Voltage Engineering
 
Recent Publications :
img-2022-Enhancement of the thermal analysis of harmonics impacts on low voltage underground power cables capacity
img-2021-Enhancing the Diagnostic Accuracy of DGA Techniques Based on IEC-TC10 and Related Databases
img-2021-Impact of Superconducting Current Limiter on the Gaseous HVDC Circuit Breakers Characteristics
img-2021-A study of multi‑break HVDC gaseous circuit breaker performance by using black box arc model
img-2021-Cascaded HVDC gaseous circuit breaker performance using black box arc model
img-2021-Enhancement of the thermal analysis of power cables installed in polyvinyl chloride (PVC) ducts under continuous and cyclic current loading conditions
img-2021-Diagnostic technique for analysing the internal faults within power transformers based on sweep frequency response using adjusted R-square methodology
img-2021-Overhead transmission lines impacts on neighboring buried metallic gas pipelines
img-2021-Mitigation of Magnetic Flux Density of Underground Power Cable and its Conductor Temperature Based on FEM
img-2021-Screening of the high voltage overhead transmission lines impacts on the neighboring metallic gas pipelines based on the distributed KOH-PCs
img-2021-Thermal performance of power cables installed in PVC ducts under dynamic loading
img-2020-Investigations of cable termination thermal analysis under continuous current loading
img-2020-Algorithm for load cycling correction to minimise the dry zone influences on the cross-linked polyethylene (XLPE) cable insulation
img-2020-On-line monitoring device for dry zone formation in the soil surrounding underground power cables
img-2019-Measurements of dielectric properties of High Density Polyethylene-Nano-Composites
img-2019-Condition assessment of power transformers based on dissolved gas analysis
img-2019-Parameters affecting the arcing time of HVDC circuit breakers using black box arc model
img-2019-Evaluations of the apparent soil resistivity and the reflection factor effects on the grounding grid performance in three-layer soils
img-2019-Prediction of Aged Transformer Oil and Paper Insulation
img-2019-DRY ZONE FORMATION SURROUNDING UNDERGROUND MEDIUM VOLTAGE CABLES DURING LOAD CYCLING
img-2018-Techniques Used for Unequally Spaced Grounding Grid Design
img-2018-Current Distribution in Grounding Grid Conductors with and without Vertical Rods Buried in Two-Layer Soil Model
img-2018-Load cycling of underground distribution cables including thermal soil resistivity variation with soil temperature and moisture content
img-2018-Investigating the effect of cavity size within medium-voltage power cable on partial discharge behavior
img-2018-Proposed three ratios technique for the interpretation of mineral oil transformers based dissolved gas analysis
img-2018-Proposed heptagon graph for DGA interpretation of oil transformers
img-2018-Cyclic Loading of Underground Cables Including the Variations of Back-fill Soil Thermal Resistivity and Specific Heat With Temperature Variation
img-2018-Experiences of withstand voltage testing by using variable frequency tuned resonant test system for extruded power cables in site
img-2017-Online monitoring of medium voltage overhead distribution lines polluted insulators severity
img-2017-Ground potential rise of faulty substations having equal and unequal spacing grounding grids conductors
img-2016-Performance of transformer differential relay at different neutral grounding resistance based on wavelet transform
img-2016-Power Transformer Incipient Faults Diagnosis Based on Dissolved Gas Analysis
img-2015-Improving underground power distribution capacity using artificial backfill materials, Ossama E. Gouda1 ✉, Adel Zein El Dein2, IET Gener. Transm. Distrib., pp. 1–8 , 2015
img-2015-Electrothermal Analysis of Low- and Medium voltage Cable Joints
img-2014-Thermal Experimental Dielectric Characterization of Cost-Fewer Low-Density Polyethylene Nano-composites, Osama GOUDA1, Ahmed THABET2 ,ELECTRICAL MATERIALS AND EQUIPMENT VOLUME: 12 j NUMBER: 5 j 2014 j DECEMBER
img-2014-Laboratory simulation of naturally polluted highvoltage transmission line insulators Osama E. Gouda1, Adel Z. El Dein2 1Electrical Power Department, Faculty of Engineering, Cairo University, Egypt 2High Voltage Networks Department, Faculty of Energy Engineering, Aswan University, Egypt, IET Gener. Transm. Distrib., 2014, Vol. 8, Iss. 2, pp. 321–327
img-2014-,“ Laboratory simulation of naturally polluted highvoltage transmission line insulators”, IET Gener. Transm. Distrib., 2014, Vol. 8, Iss. 2, pp. 321–327
img-2014-Osama E. Gouda, Adel Z. El Dein,“ Experimental Techniques to Simulate Naturally Polluted High Voltage Transmission Line Insulators,“ IEEE Transactions on Dielectrics and Electrical Insulation Vol. 21, No. 5; October 2014, PP.20199-2005
img-2014-Mohamed Awaad, Omar M. Salim, Ossama E. Gouda and Ebtisam M. Saied,“ Improved Kalman Filtered Neuro-Fuzzy Wind Speed Predictor For Real Data Set Collected At Egyptian North-Western Coast”, IJMER ,ISSN: 2249–6645 ,Vol. 4 , Iss.9, Sept. 2014 ,PP. 9-18.
img-2013-Effect of electromagnetic field of overhead transmission lines on the metallic gas pipe-lines
img-2013-Osama E. Gouda, Adel Z. El Dein and I. Moukhtar, “A Novel Turn to Earth Fault Modeling of Power Transformer Based on Symmetrical Components”,IET Generaton ,Transmission and Distribution, 2013 , Vol.7,PP. -716.
img-2012-Osama E. Gouda, Adel Z. El Dein and I. Moukhtar, “A Novel Turn to Earth Fault Modeling of Power Transformer Based on Symmetrical Components”, 15th MEPCON 2012, Fifteenth International Middle East Power Systems Conference (MEPCON’12), Alexandria, Egypt, December, 23-25, 2012.
img-2012-Osama E. Gouda, and Adel Z. El Dein, “Mitigation of Magnetic Field under Double-Circuit 220 kV Overhead Transmission Line”, 15th MEPCON 2012, Fifteenth International Middle East Power Systems Conference (MEPCON’12), Alexandria, Egypt, December, 23-25, 2012.
img-2012-Osama E. Gouda, and Adel Z. El Dein, “Parameters Affecting the Lightning Electromagnetic Field Waveforms”, 15th MEPCON 2012, Fifteenth International Middle East Power Systems Conference (MEPCON’12), Alexandria, Egypt, December, 23-25, 2012.
img-2012-98-Osama E. Gouda, Adel Z. El Dein, and Mostafa A. H. El-Gabalawy, “Transmission Lines Electromagnetic Field Effects on Gas Pipe-Lines”, 15th MEPCON 2012, Fifteenth International Middle East Power Systems Conference (MEPCON’12), Alexandria, Egypt, December, 23-25, 2012.
img-2012-Conventional and Un-Conventional Partial Discharge Detection Methods in High Voltage XLPE Cable Accessories
img-2011-87- O.E.Gouda , D.K. Ibrahim , D.H.Helmi , D.M.Khalifa and G.M.Amer , “Comparitive performance study on using fixed vs. adaptive variable dead time SPAR in the 500 kV transmission network”SSD 11 , 22-25 March 2011 Sousse , Tunisia
img-2011-87- O.E.Gouda , D.K. Ibrahim , D.H.Helmi , D.M.Khalifa and G.M.Amer , “Comparitive performance study on using fixed vs. adaptive variable dead time SPAR in the 500 kV transmission network”SSD 11 , 22-25 March 2011 Sousse , Tunisia
img-2011-Ossama Gouda , Ghada Amer , Tamer El-Khodary, “Transient response of grounding grid system simulation”SSD 11 , 22-25 March 2011 Sousse , Tunisia
img-2011-90- Osama E. Gouda and Adel Z. El Dein ,“Increasing the Under-Ground Cables Ampacity by Using Artificial Backfill Materials”, International Journal of Electrical Energy Systems, IJEES, Vol.3 No.2 2011.
img-2011-Osama E. Gouda and Adel Z. El Dein , “Effect of the Formation of the Dry Zone around Underground Power Cables on Their Ratings”, IEEE Transactions on Power Delivery , VOL. 26, NO. 2, PP. 972 - 978, APRIL 2011.
img-2010-Osama E. Gouda and Adel Z. El Dein , “Effect of dry zone formation around underground power cables on their ratings”, ELETRICIDADE MODERNA (EM) AGOSTO, 2010, pp. 130-142, in Portuguese.
img-2010-Osama E. Gouda, A. Thabet, and M. Abdrbo, “Developing Dielectric Properties of Industrial Insulating Materials by Nano-Technology Techniques” Published in Fourteenth International Middle East Power Systems Conference Cairo, Egypt, December 19-21, 2010 (MEPCON'10).
img-2010-Osama E. Gouda, Y. A. Mobarak, and M. Samir, “A Simulation Model for Calculating the Dielectric Properties of Nano-Composite Materials Comprehensive Inter-Phase Approach" Published in Fourteenth International Middle East Power Systems Conference Cairo, Egypt, December 19-21, 2010 (MEPCON'10).
img-2010-O.E.Gouda , G.M.Amer & H.Ibrahim.“Earth surface potentials around GPR of substation grounding”. IJPEGT , Vol. 1 , No. 2 , July – Dec. 2010 , Pages 93 – 100 .
img-2010-M.M. AWAD, F. TAHOUN, A. EL FARASKOURY, O.E. GOUDA“On-site commissioning test and diagnostics of 220 kV XLPE cable system” cigre ,2010 B1-304.
img-2010-Ossama E. Gouda , Adel Zein and Ghada Amer , “Improving the under ground cables ampacity by using artificial backfill materials” Published in Fourteenth International Middle East Power Systems Conference Cairo, Egypt, December 19-21, 2010 (MEPCON'10).
img-2010-Ossama E. Gouda , Adel Zein and Ghada Amer, “ Parameters affecting the back flashover voltage across the overhead transmission line insulator caused by lightning” Published in Fourteenth International Middle East Power Systems Conference Cairo, Egypt, December 19-21, 2010 (MEPCON'10).
img-2009-Ossama E. Gouda , Ghada M. Amer and Waleed A. Salem “ Computational aspects of electromagnetic fields near H.V. Transmission lines ” Energy and Power Engineering. 2009 , PP. 65-71.
img-2009-76-Ossama E. Gouda , Adel Z. El-Dein and Ghada M. Amer, “Effect of the formation of the dry zone around underground power cables on their ratings”International Journal of Emerging Electric Power Systems , Vol. 10 , 2009 , Issue 3.
img-2009-Ossama E. Gouda , Adel Z. El-Dein and Ghada M. Amer, “Effect of the formation of the dry zone around underground power cables on their ratings”. 20th International Conference and Exhibition on Electricity Distribution (CIRED 2009)
img-2009-Ossama E. Gouda , Adel Z. El-Dein and Ghada M. Amer, “Effect of the formation of the dry zone around underground power cables on their ratings”. 20th International Conference and Exhibition on Electricity Distribution (CIRED 2009)
img-2009-Ossama E. Gouda , Adel Z. El-Dein and Ghada M. Amer, “Effect of the formation of the dry zone around underground power cables on their ratings”. 20th International Conference and Exhibition on Electricity Distribution (CIRED 2009)
img-2009-Ossama E. Gouda , Adel Zein and Ghada Amer , “Effect of high frequency electromagnetic fields on homogenous human head models ”.6th International Multi Conference on System Signals and Devices, 2009.
img-2009-Osama E. Gouda and Adel Z. El Dein, “Effect of dry zone formation around underground power cables on their ratings”, 20th International Conference and Exhibition on Electricity Distribution, CIRED 2009, Prague, 8-11 June 2009, Paper 0120.
img-2009--Osama E. Gouda and Adel Z. El Dein , “Effect of dry zone formation around underground power cables on their ratings” International Journal of Emerging Electric Power Systems: Vol. 10 : Issue 2, Article 1. 2009
img-2009--Osama E. Gouda and Adel Z. El Dein , “Effect of dry zone formation around underground power cables on their ratings” International Journal of Emerging Electric Power Systems: Vol. 10 : Issue 2, Article 1. 2009
img-2009-Osama E. Gouda and Adel Z. El Dein, “Comparative Methods for Reducing the Electromagnetic Fields under Overhead Transmission Lines” CIGRE, GGG POWER 2009, Conference & Exhibition, Doha- Qatar
img-2006-O.E.Gouda et al "Optimum design of grounding system in uniform and non-uniform soils using ANN", IPEC 2006 conference, Philadelphia University/ Jordan, during the period 19-21 September 2006.
img-2006-O.E.Gouda et al "Optimum design of grounding system in uniform and non-uniform soils using ANN", International Journal of Soft Computing 1(3):181-183, 2006.
img-2006-O.E.Gouda et al "Computation of potential profile at a surface above energized unequally spaced grounding grid" MEPCON 2006 conf., Elminia University/ Egypt.
img-2006-O.E.Gouda et al "Analysis and design of control systems using artificial Intelligent" MEPCON 2006 conf., Elminia University/ Egypt.
img-2006-O.E.Gouda et al "Effect of high frequency electromagnetic field on human head using multi-layer model"8th International Middle Eastern Simulation Multi-conference August 28-30 2006, Alexandria, Egypt
img-2005-O.E.Gouda et al “Factors affecting the apparent soil resistivity of multi-layer Soil”. 14th International Symposium on High Voltage Engineering (ISH 2005) being held on August 25-29, 2005 at Beijing International Convention Center, Beijing, China
img-2005-Osama E. Gouda and Adel Z. El Dein , “Computational Aspects to Study the Effect of Electrostatic Field of High Voltages Transmission Lines on the Human Body” Asian Journal of Information Technology, Vol. 4, No. 4, pp. 339-347, 2005.
img-2004-O.E.Gouda et al" Computational aspects to study the effect of electrostatic field of high voltages transmission lines on the human body" CATAEE, March (2004), Amman. Jordan.
img-2004-O.E.Gouda et al “Computational Safety analysis of grounding grid with different structure”, MESM 2004, Philadelphia University, Jordan.
img-2004-“Factors Affecting The Leakage Current Bursts of High Voltage Polluted Insulators” GD2004 Conference, UK.
img-2004-O.E.Gouda et al “Factors affecting the leakage current bursts of high voltage polluted Insulators”, 39th International Universities Power Engineering Conference 6th, September 2004, UWE Bristol, UK.
img-2001-O.E. Gouda, G.M.Amer “New digital relaying for high voltage transmission lines by using sinusoidal wave algorithms “MEPCOM 2001, Egypt.
img-2001-O.E. Gouda, Omar Tamim “A new theoretical model of water treating mechanism in solid insulation of power cables “MEPCOM 2001, Helwan, Egypt 2001.
img-2001-O.E.Gouda et al “ New digital relaying for high voltage transmission lines by using sinusoidal wave algorithms” MEPCOM 2001, Helwan, Egypt.
img-2000-O.E.Gouda and MB.Eteiba “Discharges of leakage current on the polluted surface of high voltage transmission line insulators” CD 2000, 3-8 Sept.2000, Glasgow, PP. 328-331.
img-1997-M.Zhirh and 0.E.Gouda “Artificial testing of contaminated high voltage outdoor insulators” 15M97, Montréal, Canada, PP.93-96.
img-1997-O.E. Gouda and M.Zhirh “Leakage current pulses of M V polluted insulators” GD, 97, 8th -12th Sept.1997.
img-1997-O.E. Gouda et al “An Improved method to calculate the current ratings of buried cables subjected to the power losses from other adjacent cables” CA TAEE-9 7, July 1997 Amman, Jordan.
img-1995-O.E. Gouda, et al “Simulation of high voltage substation earthing in case of uniform and non-uniform conditions” Cigre, 21-23 January 1995, Cairo, Egypt.
img-1995-O.E.Gouda and E.A.El-Sayed “New approach for thermal breakdown analysis of solid dielectric” 9th ISM, 1995, PP.No. 1017.
img-1995-O. E. Gouda et al “Suggested technique for washing the energized polluted high voltage insulators” ISM, 1995, PP No.3186.
img-1994-O.E. Gouda, H.H.El-Tamaly and E.A.El-Sayed “Live washing simulation of polluted M V insulators in laboratory” Journal of Engineering and applied science, vol.41, No.5. Oct.1994, PP1013-1028, Faculty of Engineering, Cairo University.
img-1994-M.Tweig, O.E. Gouda and Mlzzularab “Study of the leakage current on high voltage polluted insulators” ICECS” 94, Cairo, Egypt, PP. 1080-1 084.
img-1994-H.MEl-Tamaly, A.G.Zeitoun, O.E.Gouda, H.Singer and E.A.El-Sayed “Simulation of human body under energized high voltage transmission line” bulletin of Faculty of Engineering, Assiut University, Vol.22, No.2, July.
img-1991-O.E. Gouda, A. G.Z Zeitoun and E.A.Eisawy “New Algorithm for determining critical flashover voltage and standard deviation from flashover probability data” ETEP, Vol.1 No. 5, September/October 1991, PP. 233-241.
img-1991-O.E.Gouda, S.S.El-Dessouky ‘Analysis and experimental work on cavity defects in solid insulation” IEEE international symposium on electrical insulation, Toronto, Canada, June 3-6, 1991, PP.217-220.
img-1991-O.E.Gouda, S.S.El-Dessouky “Computation of the electrostatic field to evaluate the compression of electric insulation in power cables” Mansoura Eng. Journal (MEJ), vol.16, No.1, June 1991, PP.114-123.
img-1991-O.E.Gouda, A.El-zein and S.S.El-Dessouky, “Electrostatic effects on the cable dielectric” IEEE, Industry applications society, the annual meeting, vol.1, Sept.28-Oct.1991, Michigan USA, PP.540-543.
img-1991-O.E.Gouda, E.A.El-Sayed “Effect of electrostatic field on the workers under overhead transmission lines” IEEE Industry applications society, Annual meeting, vol.1 Sept.28-Oct. 4,1991, Michigan USA, 544-549.
img-1991-O.E.Gouda, A-B.Mahdy and A.A.El-Emary “The reliability of the Egyptian network in respect of the pollution severity” 7th Int. symposium on high voltage Engineering, Techniques universitat Dersden, August, 26-30, 1991. P.44.02, PP. 259-262.
img-1991-O.E. Gouda, A.A.Rasmi “Insulation life time under voltage stresses and thermal effects” 7th Int. Symposium on high voltage Engineering, Technichs Universitate Dersden August, 26-30, 1991, P.23-10, PP.231-234.
img-1991-O.E. Gouda, “Electrical discharges on the surfaces of high voltage polluted insulators”, 7th Int. Symposium on high voltage Engineering, Technichs Universitate Dersden August, 26-3 0, 1991, P.43.03, PP.175-178.
img-1991-O.E. Gouda “Factors affecting the conductivities of polluted layers of H. V T.L. insulators” 7th Int. Symposium on high voltage Engineering, Technichs Universitate Dersden August, 26-30,1991, P. 44.08, PP. 283-286.
img-1991-O.E.Gouda, A.G.Zeitoun, H.El-Hazaly, Ezzat A. Eisawy “A new algorithm for determining critical flashover voltage and standard deviation from flas hover probability data: 7th Int. Symposium on high voltage Engineering Technichs Universitate Dersden August, 26-30, 1991, P.54.02, PP.147-150.
img-1991-O.E.Gouda, A.El-zein and S.S.El-Dessouky “A new experimental technique to measure the electrostatic force in the cable dielectric” Mansura Engineering Journal (MEJ) Vol.16, No.1, June 1991, PP.124-13 1.
img-1991-O.E. Gouda, N.Tweig and M.A.Izzularab “Voltage distribution inside the high voltage power line polluted insulators” JIPSC Amman-Jordan, PP.104-109.
img-1990-O.E.Gouda, “Influence of pollution on H.V. Insulators” IEEE Int. Symposium on electrical insulation, Toronto, Canada June 3-6, 1990, PP.195-198.
img-1990-O. E. Gouda “Fl as hover of overhead H.V.T.L insulators under desert pollution conditions Proc. of conference on Elect. Insulation and dielectric phenomena (CEIDP) sponsored by the IEEE Dielectrics and Electrical Insulation Society 28-3 1 October, 1990, Pennsylvania, USA PP, 605-611.
img-1990-O.E.Gouda, A.G.Zeitoun and Ezzat A.Eisawy “A Computer Program for determining the critical flashover voltage and standard deviation using maximum likelihood method” AMS press, vol.28, No.2, 1990, PP.1-14.
img-1989-O.E.Gouda and A.A.Rasmi “Effect of the time and voltage on the critical temperature of Epoxy Resin “Scientific Engineering Bulletin, Faculty of Engineering, Cairo University, Vol. 36, No: 1, March, 1989, PP. 20 7-214.
img-1989-S.S.El-Dessouky, O.E.Gouda, A.A.Rasmy and S.A.Solyman “Effect of surface and internal discharges on breakdown of polymeric insulation” Proc. of the AEC’89, Al­-Azhar engineering first conference December 9-12, 1989, vol.10 PP. 15-26.
img-1989-0. E. Gouda, A. El-Morshedy, A.G. Zeitoun, N.R.. Nessem “Modified technique for testing the contaminated high voltage outdoor insulators”. Middle East power system conference MEPCON 89, Vol.1 Paper no.E E16-089, PP. 184-188, January 9-13, 1989, Cairo.
img-1989-O.E.Gouda, A.G.Zeitoun and Ezzat A.Eisawy “Computerized techniques for determining the critical flashover voltage from flashover probability data” AEC,89,El-Azhar Engineering first conference December 9-12, 1989, Vol.10, PP. 75-89.
img-1989-O.E.Gouda “Analysis of thermal breakdown of solid dielectrics” Sixth Int. Symposium on high voltage Engineering 28 August-1sl Sept.1989. New Orleans, Louisiana, USA In Cooperation, Organizations, IEEE and Cigre, PP. 13.05.
img-1989-O.E. Gouda, A.A.Rasmi, S.S.El-Dessouky and S.A.Solyman “Breakdown characteristics of the insulating materials, Polystyrene PS, Polyvinyle chloride PVC and Baklite Ba, Proc. of the Sixth Int. Symposium on high voltage Engineering, New Orleans, LA, USA. August 28- September. 1, 1989, PP.No.21.5.
img-1989-O.E.Gouda, A.A.Rasmi, S.S.El-Dessouky and S.A. Solyman “Breakdown characteristics of the insulating materials, Polystyrene PS, Polyvinyl chloride PVC and Baklite Ba” Journal of the Egyptian Society of Engineers vol.28, No.2, 1989,PP. 53-5 7.
img-1989-O.E. Gouda “A simplified method to calculate the current rating of high voltage underground cables taking into account a dried out zone” AEC’89, Al-Azhar Engineering, first conf. December 9-12,1989; Vol. 10,PP. 117-127.
img-1988-O.E. Gouda, A.El-Morshedy and H.El-Ghazaly “Simulating the desert environments of high voltage polluted insulators” IX Int. Conf. on Gas Discharges and their applications. Venezia, 19-23 Sept. PP. 471-4 74, 1988.
img-1988-M. Khalifa, A, El-Morshedy, O.E. Gouda and SE. -D.Habib “A new Monitor for pollution on power line insulators” Part II Simulated Field Tests “. lEE Procedings, Vol.135, Pt. C, No. 1, January 1988, PP. 24-30.
img-1987-S.S.El-Dessouky, A.A.Rasmi and O.E.Gouda “Experimental work for the resistance of high voltage laboratory earthing grid at Port-Said of Egypt” Proc. Of Int.AMSE conf. Modelling and Simulation, Cairo Egypt, March, 2-4, 1987, vol. 2B, 13 3-140.
img-1987-O.E.Gouda, S.S.El-Dessouky “Effect of electrostatic force on the dielectric of he three phae under ground cables “Pro. Of Int. AMSE conf. Modelling and Simulation, Cairo Egypt, March, 2-4, 1987, vol. 2B, P.115-124.
img-1987-O.E.Gouda, A.El-Morshedy “Laboratory simulation of natural pollution conditions of high voltage insulators” Proceedings of the first symposium on electrical power system in fast developing countries, March 12-24,1987, Riyadh in cooperation with the IEEE, Region 8.
img-1987-O.E. Gouda “Thermal analysis of natural cooling sealing ends of h.v. cables with or without heat pipes “. Proceeding of the first symposium on electric power system in fast developing countries, March 2l-24, 1987, Riyadh in cooperation with the IEEE, Region8.
img-1987-O.E. Gouda “Current rating of high voltage cables with respect to dried out zone formation” 12 Int. Congress for statistics, computer science, social and demographic research, Cairo, 28 March-2 April, 1987.
img-1987-O.E. Gouda, A.El-Morshedy “Factors affecting the dry band formation on energized polluted insulators” Fifth Int. symposium on high voltage, Braunschweig 24-28 August 1987. Federal Republic of Germany, No.52, 08.
img-1987-A.El-Morshedy, O.E.Gouda “Laboratory Simulation of natural pollution conditions of high voltage insulators” Ffth Int. symposium on high voltage, Braunschweig, 24-28 August 1987. Federal Republic of Germany, No.52,17.
img-1987-M.Khal{fa, S.E.-D. Habib, A.El- Morshedy, O.E.Gouda “An Intelligent monitor for ezternal insulation of high voltage power network” Cigree Symposium Viennsa,5-7 May 198 7-PP.S 05-8 7.
img-1986-O.E.Gouda, S.KHindawi “The dried out zone formation around under-ground cables, analysis and computation” 11th Inter. Congress for statistics computer Science Social and Demographic Research, Cairo, Egypt 29 March-3 April, 1986.
img-1986-O.E.Gouda, S.S.El-Dessouky “Effect of electro-Static Force on the thermal-mechanical breakdown of cable dielectric” Proceedings of Int. AMSE conf. Modeling and Simulation, Sorrento Italy Sept. 29-Oct.1, 1986, Vol.2. 3, PP. 61-70.
img-1986-O. E. Gouda “Formation of the dried-out zone around under ground cables loaded by peak loading ‘Modeling simulation and control, A,AMSE Press, Vol. 7,No. 3,1986.
img-1985-Ahdab El-Morshedy, O.E. Gouda and ZA.M Yusuf “A study of leakage currents on polluted insulators” Proceedings of Jordan International Electrical and Electronic Engineering conference, April 28—May 1, 1985,PP.309-314.
img-1985-G.Koopmans, O.E. Gouda “Transport of Heat and Moisture in soils with Hysteretic Moisture potential” Proceedings of the Fourth Inter. Conference Held in Swansea, UK on 15th – 18th July, 1985,PP,846-8 74, Vol.2 Section].
img-1984-O.E. Gouda and A.El-Morshedy “Thermal analysis of an Energized polluted insulator” Proceeding Int. AMSE Conf Modelling and simulation, Athens, June, 2 7-29, 1984, Vol.3.2.
img-1983-MMAbdel Aziz, O.E.Gouda “New method for cable joint cooling” African Electrical Technology Conference, 7-9 December, 1983 — IEEE Region 8.
img-1983-MMAbdel Aziz, O.E. Gouda and M.S. Abo-Seda “Field distribution around heat pipe inside cable joints “IEEE IA S-1983 Annual meeting, Oct. 3-7, 1983, PP, 1118-1121.
img-1979-H.Anis and O.E. Gouda “Behavior of desert polluted insulators under transient voltages. Third Inter. Symposium on High voltage Engineering, Milan, 28-31 August, 1979.
img- 2014-Experimental Techniques to Simulate Naturally Polluted High Voltage Transmission Line Insulators
img--
Recent Books :
img-2016-Environmental Impacts on Underground Power Distribution (Advances in Computer and Electrical Engineering)
img-2016-Environmental Impacts on Underground Power Distribution (Advances in Computer and Electrical Engineering) by Osama El-sayed Gouda (Author), ISBN-13: 978-1466665095 ISBN-10: 1466665092
img-2012-Transmission Line Integrated Protection and auto-Re-closure Scheme, published by LAMBERT Academic Publishing
Conferences :
img-2010-O.E.Gouda, A.El-Faraskoury , F.Tahoun and M.Awad “Investigation of partial discharge measurement for H.V. cable system with variable frequency” Published in Fourteenth International Middle East Power Systems Conference Cairo, Egypt, December 19-21, 2010 (MEPCON'10).